Alarms are the cheapest life-safety item a building has and the one most often out of compliance, because responsibility for them sits exactly on the line between the unit and the common elements. Two Illinois statutes set the requirements. Neither was written with condominiums in mind, which is part of the problem and most of the reason to settle your association's position in writing.
Where must smoke detectors be?
Section 3 of the Smoke Detector Act sets three placement rules that matter to a condominium building.
Every dwelling unit must be equipped with at least one approved smoke detector in operating condition within 15 feet of every room used for sleeping purposes. The detector must be installed on the ceiling at least 6 inches from any wall, or on a wall between 4 and 6 inches from the ceiling. A "dwelling unit" under the Act includes each living unit of a multiple family residence and each living unit in a mixed-use building.
Every structure containing more than one dwelling unit, or containing at least one dwelling unit in a mixed-use structure, must contain at least one approved smoke detector at the uppermost ceiling of each interior stairwell, installed on the ceiling at least 6 inches from the wall, or on a wall between 4 and 6 inches from the ceiling.
That second rule is squarely the association's. Interior stairwells are common elements. If nobody on your board can say when the stairwell detectors were last tested, that is this month's work.
The Act's third placement rule — a detector on every story including basements, with a specific rule for split levels — is directed at single family residences, so it reaches a detached home in an association rather than a unit in a multi-unit building.
What about carbon monoxide alarms?
Section 10 of the Carbon Monoxide Alarm Detector Act requires that every dwelling unit be equipped with at least one approved carbon monoxide alarm in operating condition within 15 feet of every room used for sleeping purposes. And separately, every structure that contains more than one dwelling unit must contain at least one approved alarm in operating condition within 15 feet of every room used for sleeping purposes.
A CO alarm may be combined with a smoke detecting device, provided the combined unit complies with the provisions applying to both and emits an alarm in a manner that clearly differentiates the hazard. Alarms may be battery powered, plug-in with battery back-up, or wired into the structure's AC power with secondary battery back-up.
Section 20 exempts two kinds of residential unit. A unit in a building that (i) does not rely on combustion of fossil fuel for heat, ventilation or hot water, (ii) is not connected in any way to a garage, and (iii) is not sufficiently close to any ventilated source of carbon monoxide, as determined by the local building commissioner, to receive carbon monoxide from that source. And a unit that is not sufficiently close to any source of carbon monoxide to be at risk of receiving it, as determined by the local building commissioner.
Note who makes that determination: the local building commissioner, not the board and not the manager. An all-electric building with no attached garage may well be exempt, but a board should not simply decide it is. Many Chicago condominium buildings have gas heat, gas water heaters or an attached garage, which puts them plainly inside the requirement.
What are the battery rules?
Section 3(e) of the Smoke Detector Act is where the sealed-battery requirement lives. For dwelling units in existence on July 1, 1988, the required detectors may be battery powered provided the battery is a self-contained, non-removable, long-term battery, or wired into the structure's AC power line, and need not be interconnected.
The battery requirement applies to battery-powered smoke detectors that:
- Are in existence and exceed 10 years from the date of their being manufactured;
- Fail to respond to operability tests or otherwise malfunction; or
- Are newly installed.
So the practical rule for a condominium is this: when a detector is over ten years old, fails a test, or is being installed for the first time, the replacement must have a sealed ten-year battery or be hard-wired. Loose nine-volt batteries are the thing being phased out, which is sensible, because a removable battery is a battery somebody removes.
The battery requirements do not apply to a fire alarm, smoke detector, smoke alarm or ancillary component that is electronically connected as part of a centrally monitored or supervised alarm system; that uses a low-power radio frequency wireless communication signal; that uses Wi-Fi or other wireless local area networking to send and receive notifications to and from the Internet, such as early low-battery warnings; or to other devices the State Fire Marshal designates.
For units newly constructed, reconstructed or substantially remodelled after December 31, 1987, Section 3(f) requires detectors permanently wired into the AC power line, interconnected so that one actuating actuates all detectors in the unit. For such work on or after January 1, 2011, hard-wired detectors must also maintain an alternative back-up power source — a battery or an emergency generator. A board approving a gut rehab in a unit should know this before the work is inspected.
Who is responsible in a condominium?
Here is the honest answer: the statutes do not say, in terms that resolve a condominium.
Section 3(d) of the Smoke Detector Act provides that it is the responsibility of the owner of a structure to supply and install all required detectors, and that the owner is responsible for making reasonable efforts to test and maintain detectors in common stairwells and hallways. It then allocates duties between owner and tenant for detectors inside a dwelling unit: the tenant tests and provides general maintenance and notifies the owner in writing of deficiencies the tenant cannot correct; the tenant replaces batteries, except that the owner must ensure batteries are operating when the tenant takes possession; and the owner must give one tenant per unit written information on testing and maintenance. The Carbon Monoxide Alarm Detector Act at Section 10(c) uses the same owner-and-tenant structure.
A condominium has no landlord and tenant in that sense. The unit owner owns the unit; the association holds the common elements. The common-stairwell-and-hallway duty maps cleanly onto the association. What the phrase "owner of a structure" means for alarms inside a separately owned unit is a legal question your association counsel should answer against your declaration — and it is worth asking, once, and writing the answer down.
Meanwhile, the board's own duty under Section 18.4(a) of the Condominium Property Act — to provide for the operation, care, upkeep and maintenance of the common elements — is not in doubt for the stairwell and hallway devices.
Does the Chicago code change any of this?
It can, and the Smoke Detector Act says so expressly. Section 3(h) provides that compliance with an applicable federal, state or local law or building code requiring installation and maintenance of smoke detectors in a manner different from the Act, but providing a level of safety for occupants equal to or greater than the Act, is deemed compliance — and that the requirements of the more stringent law govern.
So a Chicago building must satisfy the city's requirements where they are stricter. This is also where the building's wider life-safety obligations sit: the alarm statutes are a floor, and a high-rise has a separate regime. See our guides to Chicago life-safety planning and the compliance calendar, and check the current city requirements with the Department of Buildings or the Fire Department rather than relying on a summary.
What are the penalties?
Both Acts attach criminal penalties. Under the Smoke Detector Act, willful failure to install or maintain a required detector in operating condition is a Class B misdemeanor, and tampering with, removing, destroying, disconnecting or removing batteries from an installed detector — other than in the course of inspection, maintenance or replacement — is a Class A misdemeanor on a first conviction. The Carbon Monoxide Alarm Detector Act at Section 15 mirrors this: willful failure to install or maintain is a Class B misdemeanor, and tampering is a Class A misdemeanor on a first conviction and a Class 4 felony on a second or subsequent conviction.
Those penalties are not the reason to act. The reason to act is that this is the cheapest intervention a board has available against the worst outcome a building can have.
What should the board do this month?
- Walk every interior stairwell. Confirm an approved smoke detector at the uppermost ceiling of each one, mounted as the Act describes. Test it. Record the date.
- Walk the hallways. Section 3(d) names common stairwells and hallways together for the testing and maintenance duty.
- Check the age of every common-area device. The manufacture date is printed on the back. Over ten years means replace, and the replacement must be sealed-battery or hard-wired.
- Settle the unit-interior question with counsel and write the answer into the rules so the next board does not have to ask again.
- Send owners a short annual notice — one page, before heating season — stating the 15-foot rule for smoke and CO alarms, the sealed-battery requirement, and how to report a problem. Keep a copy and the send date.
- Ask about CO specifically. If the building has gas heat, gas water heating or an attached garage, the exemption does not apply. If you think it might, ask the local building commissioner rather than deciding internally.
- Check renovation permits. A unit undergoing substantial remodelling needs hard-wired, interconnected detectors with back-up power. Make it a condition of the association's alteration approval.
- Keep the log. Date, location, device age, test result, action taken. This is the document that matters afterwards, and it costs nothing to keep.
- Pair it with the rest of the winter list — the frozen pipes checklist and the emergency planning checklist.
How Stellar helps
Stellar inventories common-area alarms by location and manufacture date, tests and logs them on a schedule, sends the annual owner notice on the association's behalf, and builds the hard-wired detector requirement into unit alteration approvals so a rehab does not quietly create a code problem. If your board does not know the age of its stairwell detectors, contact our office or see our maintenance coordination and high-rise management services.
This article is general information for Illinois community association boards and is not legal or code advice. It summarizes the Smoke Detector Act and the Carbon Monoxide Alarm Detector Act as enacted. Who is responsible for alarms inside a separately owned unit, and what your local code requires, are questions for association counsel and your municipality.